▲適用范圍
適用于額定頻率50/60Hz,額定電壓230/400VAC的主配電柜或分配電柜(LPZ0b-LPZ1區(qū)或LPZ1-LPZ2區(qū)),
對(duì)電源第I或II級(jí)的雷擊或浪涌引起的過(guò)電壓進(jìn)行保護(hù),減輕過(guò)電壓對(duì)設(shè)備造成的損害。
選型依據(jù)標(biāo)準(zhǔn):GB/T18802.11(IEC/61643-11),GB50343
型號(hào) | 貨號(hào) | 描述 |
LDY-40B+C/1P-385 | CY603043 | Uc: 385V~,In(8/20μs):40kA,T2,1P |
LDY-40B+C/2P-385 | CY603044 | Uc: 385V~,In(8/20μs):40kA,T2,2P |
LDY-40B+C/3P-385 | CY603045 | Uc: 385V~,In(8/20μs):40kA,T2,3P |
LDY-40B+C/4P-385 | CY603046 | Uc: 385V~,In(8/20μs):40kA,T2,4P |
LDY-40B+C/1P-385H | CY603090 | Uc:385V~,Iimp(10/350μs):12.5kA,T1+T2,1P |
LDY-40B+C/2P-385H | CY603091 | Uc:385V~,Iimp(10/350μs):12.5kA,T1+T2,2P |
LDY-40B+C/3P-385H | CY603092 | Uc:385V~,Iimp(10/350μs):12.5kA,T1+T2,3P |
LDY-40B+C/4P-385H | CY603093 | Uc:385V~,Iimp(10/350μs):12.5kA,T1+T2,4P |
▲主要技術(shù)參數(shù)
電網(wǎng)額定電壓 (Un): 230V/400V~
額定頻率:50/60Hz
zui大持續(xù)工作電壓 (Uc): 385V~
標(biāo)稱(chēng)放電電流 (In@8/20μs): 40kA(T2)
zui大放電電流 (Imax@8/20μs): 80kA(T2)
沖擊電流 (Iimp@10/350μs): 12.5kA (H型,T1)
電壓保護(hù)水平 (Up) : 2.2kV
泄漏電流(@75%U1mA): <20μA
試驗(yàn)類(lèi)別: T2/T1+T2(H型)
工作溫度: -40°C ~ 80°C
相對(duì)濕度(25°C): ≤95%(無(wú)凝露)
后備保護(hù)斷路器: LDYB-80